75 kVA / 82.5 kVA / 100 kVA / 125 kVA

TECHNICAL SPECIFICATIONS

PARAMETERS DG MODELS
Duty (Standby/ Prime) Prime Prime Prime Prime
50 HZ PRIME Rating(kVA) 75 kVA 82.5 kVA 100 kVA 125 kVA
Rated(kWe) 60 66 80 100
Engine Model 41035 GM-C2 41125A GM-C2 mPower41265G mPower41565G mPower61565G
No of Cylinders 4 4 4 4 6
Phase / Voltage (V) 3 / 415 3 / 415 3 / 415 3 / 415 3 / 415
Power Factor 0.8 (lagging)
Current (A) 104.4 114.8 139 173.7
Governing class G2
Starting system 12 V DC Elec 12 V DC Elec 12 V DC Elec 24 V DC Elec
Fuel tank capacity 180 160 250
Genset Dimension (LxWxH $$) (mm) Approx. 3000 X 1150 X 2135 2950 X 1075 X 1575 3500 x 1230 x 1425
Genset Weight (kg) approx. 1350 1500 1650 1650 1855
Rated Speed RPM 50/1500
Engine Specification
Make / Series Mahindra Mahindra mpower
Power Output# (HP) 103 111.5 126 156
Aspiration Turbocharged Intercooled Turbocharged Aftercooled
Bore x Stroke (mm) 96 x 122 96 x 132 105 x 137
Displacement (Lit) 3532 3882 4800 7200
Fuel consumption @ 75% load (lit/hr) ^ 13.5 13.5 17.3 21.4
Fuel consumption @ 100% load (lit/hr) ^ 17.8 18.1 23.1 28
Lube oil specification SAE15W40 CI4 SAE15W40 CI4 SAE 15W40CI4+
Total lubrication system capacity (lit) 10 13.5 13.5 13.5 20.2
Lube Oil Consumtion (lit/hr) $ 0.1% of Fuel Consumption < 0.1% of Fuel Consumption
Lube oil change period (hrs.) 300 hrs. for Oil Top Up
600 hrs. for Oil change
500
Radiator coolant capacity (liter) 19 19 19 22.5
Alternator
Make CG/LS CG/LS/Stamford/Equivalent
Enclosure Type IP23
Voltage regulation ±1%
Class of insulation Class H
Maximum Unbalanced Load across Phases 25%

All Specifications are at Standard NTP operating conditions
^ Considering 0.845 Specific Gravity of diesel, +5 % Tolerance
# Engine Power at 110 % load
Fuel -High Speed diesel (HSD IS 1460:2005)
* Represent the Standby Ratings
$ Considering 0.89 Specific Gravity of Oil
Engine Power will have ± 5 % Tolerance
** For CG only 3 Phase Configuration available
$$Height Without Silencer