250 kVA / 320 kVAPrint

Genset Specification
Genset Prime Rating (kVA) * 250 320
Genset Prime Rating (KW) 200 256
Phase / Voltage (V) 3 / 415 3 / 415
Power Factor 0.8 (lagging) 0.8 (lagging)
Current (A) (3Phase) 348 445
Frequency (Hz)& RPM 50/1500 50/1500
Governing class G2 G2
Starting system 24 V DC Elec 24 V DC Elec
Fuel tank capacity 425 570
Genset Dimension (LxWxH) (mm) Approx. 3990 x 1500 x 1770 4550 X 1600 X 1780
Genset Weight (kg) approx. 3300 3550
Engine Specification
Make / Series Mahindra mPower Mahindra mPower
Engine Model mPower63105G mPower63905G
Rated Power at 100% Load @ 1500 RPM (HP) 310 390
Aspiration Turbocharged Aftercooled Turbocharged Aftercooled
No. of cylinders 6 6
Bore x Stroke (mm) 116.6 x 146.1 116.6 x 146.1
Displacement (Lit) 9.3 9.3
Fuel consumption @ 75% load (lit/hr) ^ 41.2 51.5
Fuel consumption @ 100% load (lit/hr) ^ 54.1 67.4
Lube oil specification 15W40 CI4+ 15W40 CI4+
Lube Oil Refil Quantity (Lit) 30 30
Lube oil consumption @ 100% load ($) 0.1% of Fuel Consumption 0.1% of Fuel Consumption
Lube oil change period (hrs.) 500 500
Radiator coolant capacity (liter) 31 45
Alternator
Make** CG/Stamford CG/LS/Stamford
Enclosure Type IP23 IP23
Voltage regulation ±1% ±1%
Class of insulation Class H Class H
Maximum Unbalanced Load across Phases 25% 25%

**Alternator Configuration available

Above specifications are subject to change without prior notice due to continuous product improvements.

All engines & alternators confirm to respective IS standards

All the genset specifications are as per ISO 8528 standard

* For Standby duty, contact Powerol authorized representative

All specifications are at standard NTP operating conditions

All the above gensets conform to the latest CPCB norms of <75 dbA